TCL Low Temperature Controller
Mode:TCL
Abstract:TCL has a long sensing capillary filled with vapor.
When any part of the component is below the temperature set point,
the contact will actuate

Specifications
Models and parameters: See below tables (calibration in standard atmospheric pressure)
Working environment:-10~70°C, <95%RH,no cond.
Sensitive element operating temperature range:-30~80°C
Electrical connection: screw terminal, 1.5mm2 wire, PG9
Electric strength: AC1500V/1min (AC1800V/1s)
Insulation resistance: ≥100MΩ in normal status, ≥10MΩ in moisture status
Sensitive element: copper capillary, φ2mm, 3m/6m long
House:cover PC, body fireproof ABS
Protection: IP54
Contact life: ≥ 105
Approval: CE
Models
Model |
Switch Contact |
Temp. Range°C |
Dead Band °C |
Capillary Length |
Temp. Limit°C |
Contact Capacitance |
|
No inductive Load |
Inductive load |
||||||
TCL-3A |
SPDT(low temp. open) |
1.0~7.5 |
2.0~4.0 |
3m |
80 |
250VAC 5A |
250VAC 4A |
TCL-6A |
SPDT(low temp. open) |
1.0~7.5 |
2.0~4.0 |
6m |
80 |
250VAC 5A |
250VAC 4A |