Многофункционален диференциален пресостат с дисплей, обхват 0-60PA, мощност 15-28V DC/AC

- Introduction
DPG Multifunction Digital Differential Pressure Gauge
Applications & Features
l Apply high accuracy MEMS sensor and digital technologies, can measure positive, negative or differential pressure. It can replace most of the traditional pointer mechanical gauges.
l It can measure fan and blower pressures, filter resistance, air velocity, furnace draft, pressure drop across orifice plates, liquid level of bubbler systems and pressure amplifier or hydraulic system.
l It can be used in medical care equipment to monitor blood and respiratory pressures.
l Suitable for surface, panel or flush mount
l Multiple ranges and engineering units selectable
l No any movable parts, no any effect on vibration
l The accuracy is up to ±1% FS
l Function keys: zero calibrate, units select, relay set, etc.
l Optional arch LED display for output and alarm
Specifications
Medium: non-combustible, non-corrosive air, not sensitive to moisture, dust, condensation and oil
Medium Temp.: 0-60°C
Materials: cast aluminum housing and PC plate
Work Environment: -20~70°C
Compensated Temp.: 0-50°C
Work pressure: 1, 2, 5 or 10Kpa for different ranges
overload 5xFS, burst 10xFS
Dimension: see diagram
Connection: 1/8” ID tubing, two pairs (on left side and back)
Display: 4 bits 0.8” red LED
Relay output: 2×SPST, 3A×30VDC/250VAC or 1×Buzzer
Accuracy: up to ±1.0% FS, see accuracy table
Long term stability: ±0.5%FS /Year
Thermal effect: <0.05%FS/°C(Zero), <0.08%FS/°C(FS)
Response time: 0.5-30s
Power: 16-28V AC/ DC, optional 85-265V AC
Key: 3 touch buttons
Protection: IP65
Weight: 340g
Approval: CE
Accessory: A-S0 is standard. Options are A-S1, A-S2 and A-S7-X. They can be used for surface, panel or flush mount and should be ordered separately. See details in Accessories.
Measuring ranges & Accuracy table
Code |
UNIT & Range |
Accuracy(%FS) |
|||||
Pa |
Pa |
kPa |
in w.c. |
mm w.c. |
mbar |
DPG |
|
1 |
0-60 |
60.00 |
0.060 |
0.250 |
6.000 |
0.600 |
3% |
2 |
0-125 |
125.0 |
0.125 |
0.500 |
12.00 |
1.250 |
2% |
3 |
0-250 |
250.0 |
0.250 |
1.000 |
25.00 |
2.500 |
1% |
4 |
0-500 |
500.0 |
0.500 |
2.000 |
50.00 |
5.000 |
1% |
5 |
0-1000 |
1000 |
1.000 |
4.000 |
100.0 |
10.00 |
1% |
6 |
0-2500 |
2500 |
2.500 |
10.00 |
250.0 |
25.00 |
1% |
7 |
0-5000 |
5000 |
5.000 |
20.00 |
500.0 |
50.00 |
1% |
8 |
0-10000 |
10000 |
10.000 |
40.00 |
1000.0 |
100.00 |
1% |
9 |
0-20000 |
20000 |
20.000 |
80.00 |
2000.0 |
200.00 |
1% |
Note: 1. For zero center models, add“Z”at the end of the model. For example, DPG1***Z, means -30-0-30pa. Only ranges 1~6 have this selection.
2. 5 engineering units can be set by the key and then the related LED will be on
Modele
Model |
DPG |
DP gauge |
||||
Range |
See table |
Ranges selection |
||||
Arch LED |
0 |
N/A |
||||
1 |
Arch LED |
|||||
Relay |
0 |
N/A |
||||
1 |
2×SPST |
|||||
2 |
1×Buzzer |
|||||
Power |
0 |
16-28V DC/AC |
||||
1 |
85-265V AC |