CMW,CMWN & CMD Carbon Monoxide (CO) Transmitter/Controller
Applications & Features
l It’s necessary to control the ventilation of car park and vehicle maintenance and test work shop according to many building HVAC regulations. Considering of energy efficiency, demand controlled ventilation (DCV) is recommended to provide enough fresh air according to CO concentration and temperature. CM transmitter and controller are designed for these applications. It can effectively control the ventilation system to safety and energy-saving operations
l Environmental friendly electrochemical sensor gives good long term accuracy, sensitivity and reliability
l Better than most other similar sensors, it gives more than 5 years sensor life to protect customer’s investment
l Better than most other similar sensors, it only need periodical recalibration as long as 3 years or more, maintain 5% accuracy
l All electrical terminals are on the inside bottom, avoid any possible destroy to PCB when wiring (for CMWN)
l Digital technology applied, multiple outputs optional, over voltage and reverse polarity protection, high reliability and anti-interference capability
l Wide range of operating temperature, optional relay to actuate the alarm or control function output
l LCD & function keys can set various parameters, calibrate and adjust output, so that the product can be a stand alone controller
Specifications
CO Sensor: Electrochemical gas sensor
Range: 0~100ppm, or other (0-400ppm)
Accuracy: ﹤±5% @ 0-400ppm
Temperature sensor: Thermistor
Range: 0~50°C
Accuracy: ±0.5°C@25°C (≥1m/s air flow)
Output: 4~20mA (3 wires), 0~10VDC, RS485 / Modbus; OUT1-: T, OUT2: CO
Relay: 2×SPST, 1A/30VDC, 0.5A /125VAC(for CMW,CMD), 3A/30VDC, 3A/250VAC (for CMWN)
Response Time: ≤60s
Output Load: ≤500Ω (current), ≥2KΩ (voltage)
Power: 15~28VAC/15~36VDC
Display & Keys:optional LCD Display & Keys(CMW/CMWN), see more details on LCD & Keys operation
Work environment: -10~60°C (continuous); -40~70°C (intermittent); 0-95%RH (Non- cond.)
Housing: fireproof ABS
Protection: IP30 (CMW/CMWN), IP65 (CMD)
Agency Approval: CE
Models
Model |
CMW/ CMWN |
Wall mount CO transmitter/ Controller |
||||
CMD |
Duct mount CO transmitter/ Controller |
|||||
Output |
1 |
4~20mA & 0~10VDC |
||||
B |
4~20mA & 0~10VDC, RS485/Modbus |
|||||
Range |
0 |
0~100ppm/0-50°C |
||||
7 |
other(0~400ppm/ 0-50°C) |
|||||
Relay output |
0 |
N/A |
||||
1 |
2×SPST |
|||||
LCD&Keys (CMW/CMWN) |
0 |
N/A |
||||
1 |
LCD |
|||||
2 |
LCD&Keys |